ZNX Counter flow Type Evaporative Condenser

Working principle
For ZNX series combined flow evaporative condenser, the fresh air intakes from bottom air inlet, and will become saturated hot air mixed with spraying water as they flow in reverse direction. The heat will be exhausted out by fans,but the water will be collected to water basin for secondary spraying by its special designed drift eliminator. As no infill inside, ZNX series combined flow evaporative condenser has much space to enlarge its coil unit heat rejection area, more compact structure and requires less footprint .
 
Advantage:
1, No infill designed, more compact structure, lower profile, less installation area required, and easy for transport and installation.
2,Suitable to severe environment as its structure muchmore close, which could prevent from sand and dust.
3, Suitable to high temperature fluid, because hot spraying water will not distort PVC fill as no PVC fill designed.
4, Freezing resistance,because there is no PVC fill to slow down spraying water flow speed.

Model Selection
1, Confirm Total System Heat Rejection Capacity: Total System Heat Rejection Capacity = Total latent heat of condensing medium inside + Total heat rejection of condensing medium (For refrigeration system, it could be
selected based on system refrigeration capacity)
2, Confirm the design conditions: Condensing Medium, Condensation Temperature, and Wet Bulb Temperature
3, Determine the correction coefficient ‘R’ by lookup correction coefficient table.
4, Determine Corrected Heat Rejection Capacity: Corrected Heat Rejection Capacity = Total System Heat Rejection Capacity * ‘R’ (correction coefficient).
5, Model selection: select the evaporative condenser model
with rated capacity equal to or greater than the Corrected Heat Rejection Capacity.
Example
(Take Ammonia refrigeration as an example)
1, Total Heat Rejection Capacity of the ammonia refrigeration system is 1200 kw. (Total Heat Rejection Capacity = Compressor refrigerating capacity + Compressor shaft power)
2, Operating condition: Condensation temperature 36 ℃, Wet Bulb Temperature 28 ℃.
3, Lookup ‘Correction Coefficient Table for R717’, and get the correction coefficient 1.35.
4, Determine Corrected Heat Rejection Capacity: 1200kw x l. 35 = 1620kw
5, According to ZHX model table of HAC evaporative condenser, select model ZHX-1680 as it’s the smallest one in these models with capacity greater than1620 kw.
Notice
1, The parameters in the datasheet is for reference only.
2, Operating weight is the weight of equipment full of refrigerant, and bottom water tray full of spraying water.
3, For client’s non-standard requirement, customization available.
4, The rated heat rejection capacity in the datasheet is calculated based on following design conditions: Condensing Temperature=37℃,Maximum Wet bulb Temperature=26℃.


MODEL

CAPACITY
(M3/h)

FAN

WATER SPRAYING PUMP

INLET/OUTLET DN(MM)

WEIGHT

DIMENSION

QTY

POWER
(K/W)

AIR VOLUME PER SET (M3/h)

QTY

POWER
(K/W)

WATER VOLUME PER SET
(M3/h)
DN(mm)
SHIPPING
(KG)

OPERATIONG
(KG)

LENGTH
(MM)

WIDTH
(MM)

HEIGHT
(MM)
ZNX-100 100 1 1.5 18000 1 0.55 23 DN50 890 1660 1230 1150 3440
ZNX-200 200 1 2.2 30000 1 0.75 28 DN50 1370 2480 1925 1150 3650
ZNX-320 320 1 3 45000 1 0.75 28 DN50 1990 3620 1925 1840 3840
ZNX-430 430 1 4 60000 1 1.1 45 DN80 2120 3790 1925 1840 4220
ZNX-525 525 1 5.5 75000 1 1.5 65 DN80 2420 4490 2470 1840 4220
ZNX-595 595 1 7.5 87000 1 1.5 65 DN80 2690 4760 2470 1840 4450
ZNX-700 700 1 7.5 100000 1 2.2 84 DN100 3650 6080 2790 1840 4450
ZNX-800 800 2 4 65000 1 2.2 84 DN100 4150 7480 3770 1840 4220
ZNX-870 870 2 4 65000 1 2.2 84 DN100 4680 8010 3770 1840 4450
ZNX-980 980 2 4 65000 1 2.2 84 DN125 5120 8450 3770 1840 4450
ZNX-1100 1100 2 5.5 75000 1 3 120 DN125 5360 9430 3770 2200 4220
ZNX-1250 1250 2 5.5 75000 1 3 120 2-DN100 5980 10050 3770 2200 4450
ZNX-1380 1380 2 5.5. 87000 1 4 170 2-DN100 6230 11270 4846 2200 4350
ZNX-1520 1520 2 7.5 100000 1 4 170 2-DN100 6560 11590 4846 2200 4650
ZNX-1680 1680 3 4 65000 1 4 170 2-DN100 7850 13730 5610 2200 4350
ZNX-1840 1840 3 5.5 75000 1 4 170 2-DN125 8450 14330 5610 2200 4650
ZNX-2010 2010 3 5.5 75000 1 4 170 4-DN80 9180 15380 6046 2200 4650
ZNX-2245 2245 3 7.5 87000 1 5.5 230 4-DN80 9780 17340 7230 2200 4650
ZNX-2450 2450 4 5.5 75000 2 3 120 4-DN100 10860 18520 7450 2200 4650
ZNX-2600 2600 4 5.5 75000 2 4 170 4-DN100 11480 20880 9030 2200 4965
ZNX-2820 2820 4 5.5 75000 2 4 170 4-DN100 11720 21120 9030 2200 4965
Notes:
1.Do not use for construction. This brochure includes data current at the time of publication which should be reconfirmed at the time of purchase
2.All location dimensions for coil connections are approximate and should not be used for prefabrication of connecting piping